Free Tool

Voltage Drop Calculator

Calculate voltage drop, find minimum wire size, or max run length for DC, single-phase, and three-phase AC solar circuits per NEC standards — free, no signup.

Voltage Drop Calculator for Solar

Select circuit type, wire size, material, and run length. Get voltage drop percentage, pass/fail status, power loss, annual energy loss, and recommended wire size.

Calculation Mode
Circuit Type    
Circuit Parameters
A
Enter the circuit current in amps Current must be 0.1–2,000A
V
Voltage must be 6–1,500V
ft
Measure one direction — formula handles return path Length must be 1–5,000 ft
Common solar: 10 AWG (strings), 6–4 AWG (home run)
%
NEC recommends ≤2% DC, ≤3% AC, ≤5% total system Must be 0.5–10%
PF
Most solar inverters output at unity PF (1.0)
Conductor Details
Copper standard for solar. Aluminum saves cost on large AC runs.
Affects AC impedance (NEC Table 9)
sets
1 = standard single run. 2+ for large commercial
×
1.25 for continuous loads (>3 hrs). 1.0 otherwise.

NEC 690.8 solar multiplier is applied automatically in Solar Options below. This override is for other adjustments only.

Solar / Loss Estimation
Auto-applies Isc × 1.25 for PV source/output circuits
strings
Strings in parallel → current multiplied
Adjusted current (NEC 690.8 applied)
$/kWh
hr/day
US average 4.0–5.5 hr/day
Voltage Drop
Enter circuit details to calculate
NEC Compliance
0%2%3%5%10%
Voltage Drop
of system voltage
VD in Volts
Delivered Voltage
at load terminal
Power Loss
watts wasted as heat
Annual Energy Loss
kWh / year wasted
Annual Cost of Losses
per year at your rate
Calculation Breakdown
  • Base current
  • NEC 690.8 × 1.25
  • Design current
  • Phase factor
  • One-way length
  • Resistance (Ω/kft)
  • Formula
  • Voltage Drop
Wire Size Comparison Same circuit · All gauges
Wire SizeVD%VD (V)Power Loss
Voltage Drop vs. Distance Interactive chart · Multiple wire sizes

Dashed lines show NEC thresholds: 2% DC limit · 3% AC limit · 5% max total. Vertical marker shows your wire run length. Highlighted line = selected wire size.

NEC Chapter 9 Resistance Reference

Conductor DC resistance at 75°C (Ω per 1,000 ft) · NEC Table 8

Wire Size DC Resistance
Ω / 1000 ft
DC Resistance
Ω / 1000 m
VD per 100 ft
at 10A (1-phase)
VD per 100 ft
at 30A (1-phase)
Free Calculator — Professional Software

Ready to design solar projects in minutes, not hours?

SurgePV combines AI-powered 3D roof modeling, bankable energy simulation, and white-label proposals in one platform. Used by solar installers to close deals faster.

3D
AI roof modeling
2 min
Average proposal time
P90
Bankable energy yield
Free
Demo · no commitment

What This Tool Covers

The Voltage Drop Calculator determines voltage loss in DC string and AC output circuits for solar installations per NEC requirements. Enter your wire size, material, run length, current, and system voltage, and it returns voltage drop in volts and percent, pass/fail status against NEC limits, power loss, annual energy loss, and the recommended wire size if you fail.

Inputs Accepted

  • • Circuit type: DC string or AC output
  • • Wire size (AWG, from 14 AWG to 750 kcmil)
  • • Wire material: copper or aluminum
  • • One-way wire run length (feet)
  • • Circuit current (amps)
  • • System voltage (V)

Outputs Generated

  • • Voltage drop in volts (V)
  • • Voltage drop as percentage (%)
  • • Pass/fail against NEC 2% DC and 3% AC limits
  • • Power loss in watts (W)
  • • Annual energy loss in kWh
  • • Recommended minimum AWG to pass NEC limits

Features

NEC Pass/Fail Status

Instantly see whether your wiring configuration meets NEC Article 690 recommendations: 2% for DC circuits, 3% for AC circuits. A clear pass/fail flag makes inspection prep straightforward.

Energy Loss Quantification

Voltage drop translates directly to wasted energy. The calculator converts power loss (W) into annual kWh loss so you can put a dollar value on wire undersizing.

Recommended Wire Size

If your current wire size fails, the tool calculates and displays the minimum AWG (for copper or aluminum) that would bring voltage drop below the NEC limit.

How It Works

1

Select Circuit Type and Wire Parameters

Choose DC string or AC output circuit. Select your wire material (copper or aluminum) and AWG size. The calculator loads the corresponding resistivity from NEC conductor resistance tables.

2

Enter Run Length and Electrical Values

Enter the one-way run length in feet (the calculator doubles it to get total conductor length for DC circuits, or uses the appropriate multiplier for AC). Input circuit current in amps and system voltage.

3

Calculate Voltage Drop

Using the conductor's resistance per 1,000 feet (from NEC Chapter 9 Table 9), the calculator computes the voltage drop across the total conductor length at the given current. This result appears in volts and as a percentage of system voltage.

4

Check Against NEC Limits and Get Recommendation

The tool compares calculated drop to the 2% DC or 3% AC threshold. If the circuit fails, it iterates through larger AWG sizes to find the minimum passing size and reports it alongside the pass/fail status.

Use Cases

Long DC String Runs

Rooftop arrays with combiner boxes far from the inverter can have DC runs exceeding 100 feet. Verify that the home-run wire size keeps voltage drop below 2% before the installation crew pulls wire.

Inverter-to-Panel AC Wiring

AC output circuits from a string inverter to the main panel can be long in homes where the inverter is in a garage or detached structure. Check that 3% AC voltage drop limit is met before sizing conduit.

Energy Loss Cost Justification

When a customer pushes back on upsizing wire, calculate the annual kWh loss from the undersized wire, multiply by the utility rate, and show the cost. Often the payback on larger wire is under 3 years.

Calculation Methodology

Voltage Drop (DC)

VD = 2 × L × R × I ÷ 1000 (R = resistance per 1,000 ft for AWG, from NEC Ch.9 Table 9)

Voltage Drop Percentage

VD% = (VD ÷ System Voltage) × 100

Power Loss

P Loss (W) = VD × I

Annual Energy Loss

Annual kWh = P Loss × Peak Sun Hours × 365 ÷ 1000

Pro Tips

1

Use Isc for DC string voltage drop. NEC 690.8 requires sizing DC conductors at 125% of Isc. Use 1.25 × Isc as the current input for DC string calculations to ensure code compliance in your wiring, not just voltage drop.

2

Aluminum is 61% as conductive as copper. If you switch to aluminum to reduce cost, you'll need a larger AWG to achieve the same resistance. The calculator handles this automatically when you select the wire material.

3

2% is a recommendation, not a hard NEC requirement. NEC 210.19(A) and 215.2(A) recommend voltage drop limits but don't mandate them as code violations. However, many AHJs enforce them during inspection, and energy loss from exceeding them is real regardless of code status.

4

Check both ampacity and voltage drop independently. A wire may have sufficient ampacity (current-carrying capacity) but fail voltage drop — or vice versa. Always verify both. The larger AWG from either check is the one to use.

Frequently Asked Questions

What NEC voltage drop limits apply to solar?

NEC recommends 2% voltage drop for branch circuits (including DC strings) and 3% for feeders (including AC output circuits). The combined recommended limit is 5% end-to-end. These are in NEC 210.19(A) informational notes and 215.2(A). Many utilities and AHJs enforce these as conditions of interconnection or permit approval.

Should I use one-way or round-trip length?

Enter one-way (single conductor) length. For DC circuits, the calculator automatically doubles it to account for the return conductor. For single-phase AC, it also doubles. This is the standard convention — entering the total wire length would double-count.

What current should I use for DC string calculations?

For NEC compliance, use 1.25 × Isc (short-circuit current from the panel spec sheet). For actual expected voltage drop during normal operation, use Imp (maximum power current). The tool lets you input either — use Imp for energy loss estimates and 1.25 × Isc for code compliance checks.

Does temperature affect voltage drop calculations?

Yes. Conductor resistance increases with temperature (copper's resistance coefficient is approximately 0.393% per degree Celsius). The NEC Chapter 9 Table 9 values are at 75°C. In high-temperature conduit installations, resistance is higher and voltage drop increases. Use the wire size calculator for temperature-derated ampacity, then verify voltage drop separately.

Is voltage drop the same as power loss?

Voltage drop (V) and power loss (W) are related but different. Power loss = voltage drop × current (P = VD × I). Voltage drop is measured in volts; power loss in watts. A circuit can have a small voltage drop percentage but significant watt loss if current is high.

Does this calculator work for microinverter systems?

Yes, for the AC trunk cable from microinverters to the panel. Microinverter systems don't have DC strings, so select AC output circuit type. Enter the total AC current from all microinverters on the branch and the trunk cable run length to the breaker panel.

How much does an oversized wire reduce annual energy loss?

Going from 10 AWG to 8 AWG (one size up) reduces resistance by approximately 37%. On a 200-foot, 10-amp DC circuit, this might reduce annual energy loss from 180 kWh to 113 kWh — a savings of 67 kWh/year, worth $10–$20 annually. Over 25 years, that's $250–$500 in recovered generation.

Ready to Build the Full NEC-Compliant Wiring Design?

SurgePV goes from voltage drop checks to a complete permit-ready design — system layout, electrical documentation, shading analysis, and proposals in one platform.

No credit card required · Full access · Cancel anytime